S cable is widely used for temporary electrical power connections requiring flexibility.
Description
S Rubber Cable
Safety approval style: S
Executed standard: UL62
Rated temperature option: 60°C, 75°C, 90°C, 105°C
Rated voltage: 600V
Insulation: EPDM rubber
Outer sheath: Neoprene rubber.
Ultra flexible softness:
Fixed installation bending radius: 4 x cable OD
Moveable installation bending radius: 6 x cable OD
Ultra flexible cable is good for applications that require tight turns.
S cable is widely used for temporary electrical power connections requiring flexibility.
The EPDM rubber insulation has good tensile strength.
Resistant to abrasion, ozone, sunlight, chemicals, oil and suitable for submersion under water.
Insulation resistance: minimum 10 mOHM per km
Flame rated cable meets requirements for preventing the spread of flames on base of a timed test.
FT1 rated cable is suspended vertically during testing.
FT2 rated cable is suspended horizontally during testing.
Reference standard: UL1581
Application: indoors and outdoors, industry equipments and devices under high humidity or water condition.
Cable structure:
Minimum insulation thickness: 0.76 mm
Minimum jacket wall thickness: 1.52 mm
Specification:
Cable spec | Conductor | Insulation O.D. | Jacket O.D. | Current |
18AWGx2C | 41/0.16 mm | 2.80 mm | 8.80 mm | 10A |
16AWGx2C | 26/0.254 mm | 3.10 mm | 9.45 mm | 13A |
14AWGx2C | 41/0.254 mm | 4.30 mm | 12.80 mm | 15A |
12AWGx2C | 65/0.254 mm | 4.65 mm | 14.12 mm | 20A |
18AWGx3C | 41/0.16 mm | 2.80 mm | 9.30 mm | 10A |
16AWGx3C | 26/0.254 mm | 3.10 mm | 9.95 mm | 13A |
14AWGx3C | 41/0.254 mm | 4.30 mm | 13.50 mm | 15A |
12AWGx3C | 65/0.254 mm | 4.65 mm | 15.35 mm | 20A |
18AWGx4C | 41/0.16 mm | 2.80 mm | 9.95 mm | 10A |
16AWGx4C | 26/0.254 mm | 3.10 mm | 10.70 mm | 13A |
14AWGx4C | 41/0.254 mm | 4.30 mm | 14.70 mm | 15A |
12AWGx4C | 65/0.254 mm | 4.65 mm | 16.61 mm | 20A |